The Fire Beam BLUE Linear app-controlled beam detector

Product reference: PSFBBlue
  • Reflective optical beam smoke detector with a motorised head;
  • App-controlled BLUE model
  • Enclosure rating: IP65;
  • Covers a range of 7 to 70m;
  • To cover distances over 70 metres just add one of our range kits to extend the coverage up to 160 metres.
  • Operating Temperature: -10⁰C / +55⁰C;
  • Quiescent current: 3,5mA;
Read more
At stores prices may vary
Price:
€431.97
€357.00 tax excl.

Product information

The XTRA has become the industry favourite and we want you to know that it still has our full support. Even with the launch of the new app-controlled BLUE model, we recognise that there will still be some applications where you want to use a wired low level controller. The XTRA still allows you to do that and that won't change. We see both the XTRA and BLUE as the leading products in our range, each suited to different applications.

The standard Fire Beam XTRA package comes complete with the head unit, the low level controller, a single reflector, a user manual and a 3mm allen key. This will enable you to cover distances up to 70 metres. To cover distances over 70 metres just add one of our range kits to extend the coverage up to 160 metres.

Electrical Specifications:
Supply Voltage 10.2 to 30 VDC
Supply Current 3.5mA (constant current) in all operational states
Constant Current 17mA (constant current) in fast commissioning
Environmental Specifications:
Temperature -10°C to +55°C
Humidity 10 to 95% RH Non-condensing
Protection Index IP65 when suitably mounted and terminated
Mechanical Specifications:
Beam Head H:180mm x W:155mm x D:137mm - Weight 1.1kg
Controller H:185mm x W:120mm x D:62mm - Weight 0.55kg
Mid Range Kit H:293mm x W:293mm x D:5mm - Weight 0.8kg
Long Range Kit H:394mm x W:394mm x D:5mm - Weight 1.8kg
Unistrut Adaptor H:270mm x W:250mm x D:5mm - Weight 0.6Kg
(mounts the Beam Head onto Unistrut)
Optical Specifications:
Optical Wavelength 870nm
Maximum Angular Alignment ±5°
Maximum Angular Misalignment (static not auto-aligning)
Beam Head ±0.75°  /  Reflector ±2°
Operational Specifications:
Protection Range
Fire Beam Xtra As standard up to 70 metres
Mid Range Kit 70 to 140 metres
Long Range Kit 140 to 160 metres
Alarm Sensitivity Levels
25% (1.25dB) to 50% (3dB) in 1% (0.05dB) increments (default 35% (1.87dB))
Alarm Condition:
Obscuration drops to below pre-defined sensitivity level.
Time to Alarm Condition adjustable between 2 to 30 seconds in 1 second increments (default 10 seconds)
Alarm Indication:
Controller Status - FIRE
Controller Red Flashing LED
Head Red Flashing LED
Alarm Relay Change Over (CO) Contact
Rating 2A @ 30 VDC
Test / Reset Features:
Beam test function by controller
Alarm latching / auto-reset selectable (default auto-reset)
Alarm reset in latching mode by controller reset function, removing power for >5 seconds, apply 12 to 24 VDC to reset connections in Beam Head.
Fault Sensitivity Level:
90%
Fault Condition:
Obscuration drops to below the fault sensitivity level within 1 second
Power Down or Supply Voltage < 9 VDC
Commissioning modes, Pre-Alignment and Auto-Alignment
Beam turned off during Beam Maintenance
Time to Fault Condition adjustable, 2 to 60 seconds in 1 second increments (default 10 seconds)
Fault Indication:
Controller Status - FAULT
Controller Yellow Flashing LED 1 Second
Head Yellow Flashing LED 1 Second
Fault Relay Change Over (CO) Contact Rating 2A @ 30 VDC
Normal Condition:
Obscuration level is above the Alarm sensitivity level
Controller Status - NORMAL
Controller Green Flashing LED
Programmable on/off
Head Green Flashing LED
Programmable on/off
Auto-Align / Beam Contamination Compensation:
Auto-align during normal operation if obscuration drops below 90% for the duration of the align time set (doesn't affect normal operating mode)
Beam Contamination Compensation 4 hour monitoring. Compensation data available at the controller

Sertificates

© UAB “Eproma” All rights reserved