Product information

ID300 Smoke and Heat detector.

The ID300 smoke and heat detector has new smoke and temperature sensing technologies. As a result, this improved –reliability detector responds well to all types of fires (especially to fast burning blazing fires involving inflammable liquids, which produce a limited amount of smoke) and is highly immune to false alarms.

The ID300 can be set to the sensitivity mode which best suits the application (by means of EDRV1000 driver).choosing from the following: 

  • 0.08 – 0.10 – 0.12 – 0.15 dB/m
  • A1R (58°C + RoR) – B (72°C) – BR(72°C + RoR) – A2S (58°C)
  • Modalità AND – OR - PLUS

Technical features:

  • power supply 10-30 V DC;
  • programmable;
  • current consumption standby 90 μA;
  • current consumption in alarm 40 mA;
  • remote output current consumption max. 14 mA;
  • operating temperature –5°C + 40°C;
  • humidity 95% (no condensation);
  • dimensions: height 54mm, weight 110mm.

The ID300 can be set to the sensitivity mode which best suits the application (by means of EDRV1000 driver).choosing from the following: 

Plus Mode (set at factory): the detector will trigger an alarm when the measured values exceed the set smoke threshold (configurable as per the ID100), or when the measured values exceed the set heat threshold (configurable as per the ID200). Furthermore, in the event of a rise in temperature, the smoke detection sensitivity will be taken to the maximum value. This operating mode, characterized by high sensitivity allows detection of fast burning blazing fires (for example, fires involving inflammable liquids such as alcohol).

OR Mode: the detector will trigger an alarm when the measured values exceed the set smoke threshold (configurable as per the ID100), or when the measured values exceed the set heat threshold (configurable as per the ID200). This operating mode, characterized by discrete sensitivity analysis, allows the detector to sense fires with a high emission of smoke and low heat output (for example, smouldering fires) and also fires with low emission of smoke and high heat output (for example, burning chemicals).

AND Mode: the detector will trigger an alarm only when the set smoke and heat thresholds (configurable as per the ID100 and ID200) are exceeded at the same time. Given the reduced response, it is necessary to evaluate the risk factor before selecting this operating mode.

SMOKE Mode: the detector will operate as per the ID100.

HEAT Mode: the detector will operate as per the ID200.

Features

Detector type Combined
Power 12V
Power 24V

Sertificates

Manufacturer

Inim develops state-of-the-art systems for antintrusion, fire detection, home automation and emergency lighting. Integrated systems of the newest design that protect and control automatically residential, commercial and institutional buildings. Inim innovates to simplify the life of the installer and the end-user by means of devices that are both easy to install and use. From design to production, from testing to marketing, every Inim product is made in Italy to be appreciated in the world.