CO and NO2 leakage detection unit, 1 zone, 1 vent. level, MCO120

Product reference: CEMCO120
  • Control panel of 1 ventilation zone with diffusion sensor brand COsensor model SCO (CO sensor) and SDN (NO2 sensor).
  • Dry contact output (COM / NA) for ventilation 1.
  • 30Vdc 0,5A output.
  • Dry contact alarm output.
  • Display 3-digit, 7-segment.
  • Dimensions: 248 x 240 x 115 mm.
  • UNE 23300 certified.
Read more
At stores prices may vary
Price:
€278.19
€229.91 tax excl.

Product information

Automatic conventional COsensor control panel with carbon monoxide (CO) and nitrogen dioxide (NO2) diffusion sensors.

This control panel provides the MiniCO120 (Ref. MCO120) and MiniCO120DVB (Ref. MCO120DVB) references with 1 zone with 20 detectors capacity.

The model ending in “DVB” refers to the fact that it has double ventilation and batteries charger.

They are particularly suitable for parking or areas that need only 1 ventilation zone or installation of a few sensors in it.

The control panel displays the maximum concentration of CO in the detection zone, activating the ventilation and alarm when a specific concentration is reached after expiry of the set delay.

It has dry contact outputs for ventilation, an auxiliary 30Vdc output and an alarm dry contact output. 

The system works with CO sensor (“SCO” reference) and NO2  sensors (“SDN” reference) in the same area.

NO2  sensors transform measures of NO2  concentration in an equivalent measure of CO, and shown it in the display as a single concentration of CO, activating the ventilation and alarm when established CO levels are reached.

The control panel allows manual activation and deactivation of ventilation.

The equipment is designed for using diffusion sensors calibrated at factory for operation throughout the useful life of their sensors, and UNE 23300 certified.

TECHNICAL FEATURES

Power supply 110/230Vac 50/60Hz
Maximum consumption 20VA at 230V/AC
Power supply fuse 4A
Battery charger 350mA 27V/DC 20ºC
Sensors by zone 20 CO / NO2
(MCO120 / MCO120DVB)
IP protection IP30
Dry contact ventilation 230Vac / 30Vdc 1A
30Vdc intensity alarm output 0,5A
30Vdc output fuse Resettable
Zone output voltage 26Vdc
Zone fuse 2A
Dry contact fault 30Vdc 1A
Dry contact alarm 30Vdc 1A
Environmental conditions -10ºC +50ºC
Dimensions 248 x 240 x 115mm
Weight (without batteries) 2kg
Standard UNE 23300

Features

Zones 1

Sertificates

© UAB “Eproma” All rights reserved